East Cambridgeshire

24 MW, about 72 MWh (3 hours, measured from its behaviour) in Mid Wales and The Midlands. Everything on this page is read from published data for the 364 days to 11 November 2026, or is labelled as an estimate.

Part of Burwell Weirs Drove BESS, one of 3 balancing units at one site totalling 126 MW. This page is the E_BURWB-3 unit alone.

What it is

Registered power24 MW balancing mechanism registration
Storage duration3 hours measured from twenty one days of behaviour
Charging zoneMid Wales and The Midlands
Connection siteEast Cambridgeshire
PostcodeCB250BP
Balancing mechanism unitE_BURWB-3

Who owns it and who trades it

Traded byEDF ENERGY CUSTOMERS LIMITEDruns several sitesconfirmed, Elexon's register
Owned bynot published anywhere we can read
UltimatelyVoltwise Power (Sandbrook Capital) confirmed source

How we know. The register names no owner. The capacity market holds a site called BURWB1 belonging to Voltwise Power Holdings Limited, which is this unit's own balancing code, and Burwell Weirs Drove is a two phase Voltwise site of about 126 MW operated by Ethical Power.

Market registers name the party that sells into the market, which for a battery is usually an optimiser under contract rather than the owner. Elexon's balancing mechanism unit register names the seller here and the name is checked against it on every build. How we tell them apart

What it earned

Line364 days to 11 November 2026
Balancing mechanism£0
Response and reserve auctions auction implied£345k
Capacity marketno agreement we can attach
Three lines together£345k

Balancing is offer revenue and does not net off the cost of the power. The response and reserve figure is the value implied by the published auction results, award quantity times clearing price times the length of the delivery window, and not a settled payment. Capacity market income is the cleared price raised for inflation where the auction set a base period, split by month on EMRS's weights. Method

Outside the balancing mechanism, derived from the meter

Elexon publishes what this unit's meter recorded every half hour. Take away the balancing volumes NESO accepted and what is left is the position the unit ran outside the balancing mechanism: its wholesale trading, its frequency response delivery, and its losses, together. This unit held a frequency response contract in 6,401 of those half hours. The energy the contract asked of it, contracted megawatts times NESO's published delivery curve at the measured grid frequency, is taken out of the position and valued at the imbalance price, because it sits outside the unit's declared position and that is the price Elexon settles it at. What remains is the traded position, valued at the market index. In 10 half hours a contract was held but the grid frequency is not yet held, so those are left in the traded position. The volumes are measured. The prices are public benchmarks, not this unit's trades. The product is derived, and is shown apart from the three measured lines above. 157 days to 5 November 2026, 42 of them still provisional in Elexon's settlement runs. Method and caveats

LineMWh or £
Metered export, what crossed the meter out8,767 MWh
Metered import, what crossed the meter in10,042 MWh
Equivalent full cycles, everything sent out over one full charge122 over 157 days, 283 a year at that rate
Apparent meter to meter efficiency87%, an ordinary battery: round trip losses alone
Balancing offers accepted0 MWh
Balancing bids accepted0 MWh
Position outside balancing, export8,767 MWh
Position outside balancing, import10,042 MWh
Of which expected response delivery, net−2,307 MWh 1,962 out, 4,269 in
Traded position, net1,032 MWh 8,897 out, 7,865 in
Traded position at the market index, sold£1.4m
Traded position at the market index, bought£713k
Traded position, net, at the index£673k
Response delivery, net, at the imbalance price−£320k −£291k at the index
Balancing and outside balancing together£353k £34.19/kW/yr

This battery connects to a distribution network. For such a unit the volumes Elexon publishes are settlement volumes: the site's own meter multiplied by the network operator's line loss factor for that half hour. The factor is usually within a few per cent of one, so the megawatt hours, cycles and efficiency above can sit a little above or below what crossed the site's meter. The money is settled on the same adjusted volumes. Method and caveats

When it moved, against when power was dear

Across every half hour this unit was metered the market index averaged £125.29. What it sent out was worth £155.81 a megawatt hour at that same index, 1.24 times the average. What it took in was worth £90.70, 0.72 times. Selling above one and buying below one is a unit positioned into the dear half hours and out of the cheap ones. It measures the half hours it chose, not the price anyone paid it, which is not published.

Checks this unit did not pass cleanly. Published anyway, because a flagged figure with its flag is more use than a blank.

  • only 157 of 364 days metered
  • the meter exceeded the 24.0 MW registration on 49 days between 2026-06-05 and 2026-11-05, peaking at 30 MW export and 30 MW import: more than this battery can do, so another asset on the same meter, a commissioning period, or a settlement run error

Where it stands

All three measured lineswhole fleet, £/kW/yr26th percentile234 units

Percentiles, so 90 means better than nine in ten of the cohort named beside it, on that measure alone, over the same 364 days. Rates are pounds per kilowatt per year, annualised over the days the unit has been on the system, the same figures the performance league ranks on. A high position in the taken-in table is not a fault: a constraint asset is paid to charge, and charging is its job.

The nearest comparables

The five nearest in size in England and Wales, and this battery among them, ranked by what each was paid for every kilowatt it holds over the 364 days to the same date. They run for about the same length of time. Same market, same rules, same weather.

BatteryMWHoursMeasured, per kW
Hyde372.5h£47.6/kW/yr
Sizing John572.5h£33.7/kW/yr
Charnock Richard272.5h£31.9/kW/yr
West Bradford292.5h£29.7/kW/yr
Atherton302.5h£26.2/kW/yr
East Cambridgeshirethis battery243h£14.4/kW/yr

See it on the map

Open the operating map here

Every figure on this page traces to a published file. If something here is wrong about your asset, the methods section says how to tell us.

Need every battery at once? The register is not offered for automated download, and bulk access is by request at hello@vitreouslabs.com.